Technical Requirements for Insulation Floor Mats in Distribution Rooms
National Standard: For distribution room voltage of 10KV, choose 8mm thickness, withstand power frequency withstand voltage test of 10000V for 1 minute without breakdown.
For distribution room voltage of 35KV, choose 10-12mm thickness, withstand power frequency withstand voltage test of 15000V for 1 minute without breakdown.
For low voltage in distribution rooms, choose 5mm thickness, below 500V, withstand power frequency withstand voltage test of 3500V for 1 minute without breakdown.